Moulded Case Circuit Breaker h3 x160 TM FIX 1P1D 16A 25kA CTC HHA014Z

EAN
3250613135942
Packaging
1 Piece

Technical properties

Architecture
  • Neutral position
    without neutral
  • Number of protected poles
    1
  • Number of poles
    1 P
Functions
  • Trip Unit
    TM F/F
  • Integrated earth fault protection
    No
  • Concurrently switching N-neutral
    No
Controls and indicators
  • Motor drive integrated
    No
Main electrical features
  • Rated operational voltage Ue
    220 / 240 V
  • Type of supply voltage
    AC
  • Frequency
    50/60 Hz
Voltage
  • Rated insulation voltage
    690 V
  • Rated impulse withstand voltage
    8 kV
  • With under voltage release
    No
Electric current
  • Rated current
    16 A
  • Thermal protection nob setting xIN
    1
  • Rating current 10°C according to IEC 60947
    22 A
  • Rating current 15°C according to IEC 60947
    21.3 A
  • Rating current 20°C according to IEC 60947
    20.6 A
  • Rating current 25°C according to IEC 60947
    19.9 A
  • Rating current 30°C according to IEC 60947
    19.2 A
  • Rating current 35°C according to IEC 60947
    18.4 A
  • Rating current 40°C according to IEC 60947
    17.6 A
  • Rating current 45°C according to IEC 60947
    16.8 A
  • Rating current 50°C according to IEC 60947
    16 A
  • Rating current 55°C according to IEC 60947
    15 A
  • Rating current 60°C according to IEC 60947
    14.1 A
  • Rating current 65°C according to IEC 60947
    13 A
  • Rating current 70°C according to IEC 60947
    11.9 A
  • Rated ultimate short-circuit breaking capacity Icu under 230V AC IEC 60947-2
    35 kA
  • Rated ultimate short-circuit breaking capacity Icu under 240V AC IEC 60947-2
    35 kA
  • Rated ultimate short-circuit breaking capacity Icu under 400V AC IEC 60947-2
    25 kA
  • Rated ultimate short-circuit breaking capacity Icu under 415V AC IEC 60947-2
    25 kA
  • Range of the thermal adjustment
    16 A
  • Rated ultimate short-circuit breaking capacity Icu under 380V AC IEC 60947-2
    25 kA
Dimensions
  • Depth of installed product
    68 mm
  • Height of installed product
    130 mm
  • Width of installed product
    25 mm
Frequency
  • Frequency
    50 to 60 Hz
Power
  • Total power loss under IN
    1.8 W
  • Power loss per pole at In
    1.8 W
Endurance
  • Electric endurance in number of cycles
    1000
  • Number of mechanical operations
    4000
Installation, mounting
  • Tightening torque
    6Nm
Connection
  • Connection cross-sect. rigid cable
    6 / 95mm²
  • Type of connection
    with screw
Cable
  • Cable Material
    Cu
Settings
  • Range of the magnetic adjustment
    600 A
Equipment
  • Number of auxiliary contacts as normally closed contact
    0
  • Number of auxiliary contacts as normally open contact
    0
  • Number of auxiliary contacts as change-over contact
    0
  • Can be accessorized
    Yes
Standards
  • European directive WEEE
    concerned
Safety
  • Protection index IP
    IP4X
Use conditions
  • Degree of pollution according to IEC 60664 / IEC 60947-2
    3
  • Altitude
    2000 m
temperatur
  • Temperature of calibration
    50 °C

Downloads

  • Product image

    Image HHA014Z  | Hager Australia

    Product Image HHA014Z

  • ProductNotice

    Image Instruction manuals for HHA014Z  | Hager Australia

    Instruction manuals for HHA014Z

    PDF
    8 MB
  • ProductECDeclaration

    Image Declaration  | Hager Australia

    Declaration

    PDF
    215 KB
  • ProductROHS

    Image RoHS certificate for HHA014Z  | Hager Australia

    RoHS certificate for HHA014Z

    PDF
    32 KB
    Image RoHS certificate for HHA014Z  | Hager Australia

    RoHS certificate for HHA014Z

    PDF
    33 KB
More documentation