HA306

HA306 LOAD BREAK SWITCH 3P 125A

HA306

LOAD BREAK SWITCH 3P 125A

Cat. Ref.:HA306
pc.
EAN No.:

3250613113063

Pack Qty.:1 pc.
ex. GST*:189.82 $ / pc.
inc. GST*:208.80 $ / pc.
Price Group:22100
Technical Characteristics
Type of order:Short thumb-grip
Number of poles:3 P
Type of pole:3 P
Type of case:Fixed built-in
Reversing switch:no
Motor drive integrated:no
Rated operational voltage Ue:380 / 415 V
Frequency:50 Hz
Rated insulation voltage:800 V
Rated impulse withstand voltage:8000 V
Rated operational current in AC21category B:125 A
Acceptable current rating with AC22 category A:125 A
Cut off current:15 kA
Rated current:125 A
Short-circuit current with gI-gG fuses:50 kA
Rated short-time withstand current 1s:2,5 kA
Rated operational current in AC21 category A:125 A
Acceptable current rating with AC22 category B:125 A
Rated operational current in AC23 category A:63 A
Acceptable current rating with AC23 category B:63 A
Total power loss under IN:17,1 W
Power loss per pole at In:5,7 W
Contact rating with 400 V in AC1:82 kW
Interlockable:yes
Width of installed product:108 mm
Fixation type:DIN rail monting or back plate monting
Connection cross-sect. rigid cable:50mm² max.
Type of connection:with screw
Motor drive optional:no
European directive WEEE:concerned
Protection index IP:IP20
Operating temperature:-20…70 °C
  • HA306
    HA306 LOAD BREAK SWITCH 3P 125A
    HA306
  • HA306 LOAD BREAK SWITCH 3P 125A
Visitors who viewed this product also viewed the following products
HA307 LOAD BREAK SWITCH 3P 160A
LOAD BREAK SWITCH 3P 160A
HA305 LOAD BREAK SWITCH 3P 100A
LOAD BREAK SWITCH 3P 100A
*All data is subject to errors and technical modifications. All prices are recommended retail prices.