•  
  • e-Catalogue
  • Downloads,
    Services & Support
  • News, Exhibitions
    & Case Studies
  • AS/NZS 3000:2018
    Wiring Rules
  • About Us

HEE970H

HEE970H MCCB h1000 3P 70kA 1000A LSI

HEE970H

MCCB h1000 3P 70kA 1000A LSI

Cat. Ref.:HEE970H
pc.
EAN No.:

3250613349783

Pack Qty.:1 pc.
ex. GST*:7,657.66 $ / pc.
inc. GST*:8,423.43 $ / pc.
Price Group:15705
Technical Characteristics
Type of order:Toggle
Type of case:Fixed built-in
Number of poles:3 P
Type of pole:3P3D
Complete device with protection unit:yes
Trip Unit:LSI
Integrated earth fault protection:no
Compatible with DIN rail mounting:no
Motor drive integrated:no
Frequency:50/60 Hz
Rated operational voltage Ue:220/690 V
Rated insulation voltage:800 V
Rated impulse withstand voltage:8000 V
With under voltage release:no
Rated ultimate short-circuit breaking capacity Icu under 400V AC IEC 60947-2:70 kA
Rated service breaking capacity Ics AC according IEC 60947-2:71 %
Breaking capacity on 1 pole with 230 V NF 60947-2:60 kA
Breaking capacity on 1 pole with 400 V NF 60947-2:9 kA
Rated ultimate short-circuit breaking capacity Icu under 230V AC IEC 60947-2:100 kA
Rated ultimate short-circuit breaking capacity Icu under 240V AC IEC 60947-2:100 kA
Rated ultimate short-circuit breaking capacity Icu under 415V AC IEC 60947-2:70 kA
Rated ultimate short-circuit breaking capacity Icu under 440V AC IEC 60947-2:65 kA
Rated ultimate short-circuit breaking capacity Icu under 690V AC IEC 60947-2:20 kA
Thermal protection nob setting xIN:0,4/0,5/0,63/0,8/0,9/0,95/1
Correction factor of rating current for 2 devices placed side-by-side:1
Correction factor of rating current for 3 devices placed side-by-side:1
Correction factor of rating current for 4 and 5 devices placed side-by-side:1
Correction factor of rating current for 6 devices placed side-by-side:1
Power loss per pole at In:62 W
Power loss per pole at 0.63*In:24,6 W
Power loss per pole at 0.8*In:39,7 W
Total power loss under IN:186 W
Total power loss at 0.63*In:73,8 W
Total power loss at 0.8*In:119 W
Tripmode:LSI
Thermal protection trip time:5/10/11/16/21 ms
Time of response when opening:10 ms
Magnetic trip delay time:100 to 200 ms
Electric endurance in number of cycles:1000
Number of mechanical operations:4000
Tightening torque:65Nm
DIN rail mounting with optional adaptator:no
Connection cross-sect. rigid cable:2x240mm²
Connection cross-sect. flexible conductor:2x240mm²
Connection:Front connection
Type of connection:Terminal
Magnetic protection nob setting xIN:2,5/5/8
Setting type In or Ith:IrTh
Range of the magnetic adjustment:5600/7000/8820/10000/10000/10000/10000 A
Motor drive optional:yes
Category of use:A
Standard text:IEC 60947-2
European directive WEEE:concerned
Protection index IP:IP4X
Altitude:2000 m
Storage temperature:-35 to 70 °C
Air humidity protection:for all climates
  • HEE970H
    HEE970H MCCB h1000 3P 70kA 1000A LSI
    HEE970H
  • HEE970H MCCB h1000 3P 70kA 1000A LSI
Visitors who viewed this product also viewed the following products
HEE971H MCCB h1000 4P 70kA 1000A LSI
MCCB h1000 4P 70kA 1000A LSI
HEE801H MCCB h1000 4P 70kA 800A LSI
MCCB h1000 4P 70kA 800A LSI
HNE800H MCCB h1000 3P 50kA 800A LSI
MCCB h1000 3P 50kA 800A LSI
HEE800H MCCB h1000 3P 70kA 800A LSI
MCCB h1000 3P 70kA 800A LSI
HNE801H MCCB h1000 4P 50kA 800A LSI
MCCB h1000 4P 50kA 800A LSI
*All data is subject to errors and technical modifications. All prices are recommended retail prices.