  • e-Catalogue
  • Downloads,
    Services & Support
  • News, Exhibitions
    & Case Studies
  • AS/NZS 3000:2018
    Wiring Rules
  • About Us

HNE971H

HNE971H MCCB h1000 4P 50kA 1000A LSI

HNE971H

MCCB h1000 4P 50kA 1000A LSI

Cat. Ref.:HNE971H
pc.
EAN No.:

3250613349769

Pack Qty.:1 pc.
ex. GST*:7,489.41 $ / pc.
inc. GST*:8,238.35 $ / pc.
Price Group:15705
Technical Characteristics
Type of order:Toggle
Type of case:Fixed built-in
Number of poles:4 P
Type of pole:4P4D N:0;50;100%
Complete device with protection unit:yes
Trip Unit:LSI
Integrated earth fault protection:no
Compatible with DIN rail mounting:no
Motor drive integrated:no
Frequency:50/60 Hz
Rated operational voltage Ue:220/690 V
Rated insulation voltage:800 V
Rated impulse withstand voltage:8000 V
With under voltage release:no
Rated ultimate short-circuit breaking capacity Icu under 400V AC IEC 60947-2:50 kA
Rated service breaking capacity Ics AC according IEC 60947-2:100 %
Breaking capacity on 1 pole with 230 V NF 60947-2:45 kA
Breaking capacity on 1 pole with 400 V NF 60947-2:9 kA
Rated ultimate short-circuit breaking capacity Icu under 230V AC IEC 60947-2:85 kA
Rated ultimate short-circuit breaking capacity Icu under 240V AC IEC 60947-2:75 kA
Rated ultimate short-circuit breaking capacity Icu under 415V AC IEC 60947-2:50 kA
Rated ultimate short-circuit breaking capacity Icu under 440V AC IEC 60947-2:45 kA
Rated ultimate short-circuit breaking capacity Icu under 690V AC IEC 60947-2:20 kA
Thermal protection nob setting xIN:0,4/0,5/0,63/0,8/0,9/0,95/1
Thermal setting current on neutral pole:0/0,5/1 In
Correction factor of rating current for 2 devices placed side-by-side:1
Correction factor of rating current for 3 devices placed side-by-side:1
Correction factor of rating current for 4 and 5 devices placed side-by-side:1
Correction factor of rating current for 6 devices placed side-by-side:1
Power loss per pole at In:62 W
Power loss per pole at 0.63*In:24,6 W
Power loss per pole at 0.8*In:39,7 W
Total power loss under IN:186 W
Total power loss at 0.63*In:73,8 W
Total power loss at 0.8*In:119 W
Tripmode:LSI
Thermal protection trip time:5/10/11/16/21 ms
Time of response when opening:10 ms
Magnetic trip delay time:100 to 200 ms
Electric endurance in number of cycles:1000
Number of mechanical operations:4000
Tightening torque:65Nm
DIN rail mounting with optional adaptator:no
Connection cross-sect. rigid cable:2x240mm²
Connection cross-sect. flexible conductor:2x240mm²
Connection:Front connection
Type of connection:Terminal
Magnetic protection nob setting xIN:2,5/5/8
Setting type In or Ith:IrTh
Range of the magnetic adjustment:5600/7000/8820/10000/10000/10000/10000 A
Motor drive optional:yes
Category of use:A
Standard text:IEC 60947-2
European directive WEEE:concerned
Protection index IP:IP4X
Altitude:2000 m
Storage temperature:-35 to 70 °C
Air humidity protection:for all climates
  • HNE971H
    HNE971H MCCB h1000 4P 50kA 1000A LSI
    HNE971H
  • HNE971H MCCB h1000 4P 50kA 1000A LSI
Visitors who viewed this product also viewed the following products
HXC021H AX contact 1NO+1NC 230VAC(h250...1600)
AX contact 1NO+1NC 230VAC(h250...1600)
HNE801H MCCB h1000 4P 50kA 800A LSI
MCCB h1000 4P 50kA 800A LSI
HNE970H MCCB h1000 3P 50kA 1000A LSI
MCCB h1000 3P 50kA 1000A LSI
HXE011H UVR 24VDC (h800-h1000-h1600)
UVR 24VDC (h800-h1000-h1600)
HNE800H MCCB h1000 3P 50kA 800A LSI
MCCB h1000 3P 50kA 800A LSI
HXE013H UVR 110-120VAC (h800-h1000-h1600)
UVR 110-120VAC (h800-h1000-h1600)
HXE015H UVR 380-415VAC (h800-h1000-h1600)
UVR 380-415VAC (h800-h1000-h1600)
HEE971H MCCB h1000 4P 70kA 1000A LSI
MCCB h1000 4P 70kA 1000A LSI
HXF030H Direct rotary handle H1250-H1600
Direct rotary handle H1250-H1600
*All data is subject to errors and technical modifications. All prices are recommended retail prices.