HNF981H

HNF981H MCCB h1600 4P 50kA 1250A LSI

HNF981H

MCCB h1600 4P 50kA 1250A LSI

Cat. Ref.:HNF981H
pc.
EAN No.:

3250613349912

Pack Qty.:1 pc.
ex. GST*:10,477.56 $ / pc.
inc. GST*:11,525.32 $ / pc.
Price Group:15815
Technical Characteristics
Type of order:Toggle
Type of case:Fixed built-in
Number of poles:4 P
Type of pole:4P4D N:0;50;100%
Complete device with protection unit:yes
Trip Unit:LSI
Integrated earth fault protection:no
Compatible with DIN rail mounting:no
Motor drive integrated:no
Frequency:50/60 Hz
Rated operational voltage Ue:220/690 V
Rated insulation voltage:800 V
Rated impulse withstand voltage:8000 V
With under voltage release:no
Rated ultimate short-circuit breaking capacity Icu under 400V AC IEC 60947-2:50 kA
Rated service breaking capacity Ics AC according IEC 60947-2:100 %
Breaking capacity on 1 pole with 230 V NF 60947-2:60 kA
Breaking capacity on 1 pole with 400 V NF 60947-2:9 kA
Rated ultimate short-circuit breaking capacity Icu under 230V AC IEC 60947-2:100 kA
Rated ultimate short-circuit breaking capacity Icu under 240V AC IEC 60947-2:100 kA
Rated ultimate short-circuit breaking capacity Icu under 415V AC IEC 60947-2:50 kA
Rated ultimate short-circuit breaking capacity Icu under 440V AC IEC 60947-2:70 kA
Rated ultimate short-circuit breaking capacity Icu under 690V AC IEC 60947-2:45 kA
Thermal protection nob setting xIN:0,4/0,5/0,63/0,8/0,9/0,95/1
Thermal setting current on neutral pole:0/0,5/1 In
Correction factor of rating current for 2 devices placed side-by-side:1
Correction factor of rating current for 3 devices placed side-by-side:1
Correction factor of rating current for 4 and 5 devices placed side-by-side:1
Correction factor of rating current for 6 devices placed side-by-side:1
Power loss per pole at In:62,5 W
Power loss per pole at 0.63*In:24,8 W
Power loss per pole at 0.8*In:40 W
Total power loss under IN:187,5 W
Total power loss at 0.63*In:74,4 W
Total power loss at 0.8*In:120 W
Tripmode:LSI
Thermal protection trip time:5/10/11/19/21/29 ms
Time of response when opening:10 ms
Magnetic trip delay time:100 to 200 ms
Electric endurance in number of cycles:1000
Number of mechanical operations:4000
Tightening torque:65Nm
DIN rail mounting with optional adaptator:no
Connection cross-sect. rigid cable:3x240mm²
Connection cross-sect. flexible conductor:3x240mm²
Connection:Front connection
Type of connection:Terminal
Magnetic protection nob setting xIN:2,5/5/10
Setting type In or Ith:IrTh
Range of the magnetic adjustment:7000/8750/11200/14000/15000/15000/15000 A
Motor drive optional:yes
Category of use:A
Standard text:IEC 60947-2
European directive WEEE:concerned
Protection index IP:IP4X
Altitude:2000 m
Storage temperature:-35 to 70 °C
Air humidity protection:for all climates
  • HNF981H
    HNF981H MCCB h1600 4P 50kA 1250A LSI
    HNF981H
  • HNF981H MCCB h1600 4P 50kA 1250A LSI
Visitors who viewed this product also viewed the following products
HNF980H MCCB h1600 3P 50kA 1250A LSI
MCCB h1600 3P 50kA 1250A LSI
HEF991H MCCB h1600 4P 70kA 1600A LSI
MCCB h1600 4P 70kA 1600A LSI
HNF990H MCCB h1600 3P 50kA 1600A LSI
MCCB h1600 3P 50kA 1600A LSI
HEF990H MCCB h1600 3P 70kA 1600A LSI
MCCB h1600 3P 70kA 1600A LSI
HNF991H MCCB h1600 4P 50kA 1600A LSI
MCCB h1600 4P 50kA 1600A LSI
HEF981H MCCB h1600 4P 70kA 1250A LSI
MCCB h1600 4P 70kA 1250A LSI
HXC001H Shunt trip Release 24V DC(h250...1000)
Shunt trip Release 24V DC(h250...1000)
*All data is subject to errors and technical modifications. All prices are recommended retail prices.