  • e-Catalogue
  • Downloads,
    Services & Support
  • News, Exhibitions
    & Case Studies
  • AS/NZS 3000:2018
    Wiring Rules
  • About Us

HEC041H

HEC041H MCCB h250 4P 70kA 40A LSI

HEC041H

MCCB h250 4P 70kA 40A LSI

Cat. Ref.:HEC041H
pc.
EAN No.:

3250613340643

Pack Qty.:1 pc.
ex. GST*:2,670.10 $ / pc.
inc. GST*:2,937.11 $ / pc.
Price Group:15235
Technical Characteristics
Type of order:Toggle
Type of case:Fixed built-in
Number of poles:4 P
Type of pole:4P4D N:0;50;100%
Complete device with protection unit:yes
Trip Unit:LSI
Integrated earth fault protection:no
Compatible with DIN rail mounting:no
Motor drive integrated:no
Frequency:50/60 Hz
Rated operational voltage Ue:220/690 V
Rated insulation voltage:800 V
Rated impulse withstand voltage:8000 V
With under voltage release:no
Rated ultimate short-circuit breaking capacity Icu under 400V AC IEC 60947-2:70 kA
Rated service breaking capacity Ics AC according IEC 60947-2:71 %
Breaking capacity on 1 pole with 230 V NF 60947-2:51 kA
Breaking capacity on 1 pole with 400 V NF 60947-2:9 kA
Rated ultimate short-circuit breaking capacity Icu under 230V AC IEC 60947-2:100 kA
Rated ultimate short-circuit breaking capacity Icu under 240V AC IEC 60947-2:85 kA
Rated ultimate short-circuit breaking capacity Icu under 415V AC IEC 60947-2:70 kA
Rated ultimate short-circuit breaking capacity Icu under 440V AC IEC 60947-2:50 kA
Rated ultimate short-circuit breaking capacity Icu under 690V AC IEC 60947-2:20 kA
Thermal protection nob setting xIN:0,4/0,5/0,63/0,8/0,9/0,95/1
Thermal setting current on neutral pole:0/0,5/1 In
Correction factor of rating current for 2 devices placed side-by-side:1
Correction factor of rating current for 3 devices placed side-by-side:1
Correction factor of rating current for 4 and 5 devices placed side-by-side:1
Correction factor of rating current for 6 devices placed side-by-side:1
Power loss per pole at In:0,6 W
Power loss per pole at 0.63*In:0,3 W
Power loss per pole at 0.8*In:0,4 W
Total power loss under IN:1,9 W
Total power loss at 0.63*In:0,7 W
Total power loss at 0.8*In:1,2 W
Tripmode:LSI
Thermal protection trip time:5/8/11/21 ms
Time of response when opening:10 ms
Magnetic trip delay time:100 to 200 ms
Electric endurance in number of cycles:1000
Number of mechanical operations:4000
Tightening torque:12Nm
DIN rail mounting with optional adaptator:no
Connection cross-sect. rigid cable:35 / 185mm²
Connection cross-sect. flexible conductor:35 / 150mm²
Connection:Front connection
Type of connection:Terminal
Magnetic protection nob setting xIN:2,5/5/10
Setting type In or Ith:IrTh
Range of the magnetic adjustment:224/280/350/448/504/532/560 A
Motor drive optional:yes
Category of use:A
Standard text:IEC 60947-2
European directive WEEE:concerned
Protection index IP:IP4X
Altitude:2000 m
Storage temperature:-35 to 70 °C
Air humidity protection:for all climates
  • HEC041H
    HEC041H MCCB h250 4P 70kA 40A LSI
    HEC041H
  • HEC041H MCCB h250 4P 70kA 40A LSI
Visitors who viewed this product also viewed the following products
HEC040H MCCB h250 3P 70kA 40A LSI
MCCB h250 3P 70kA 40A LSI
HEC125H MCCB h250 3P 70kA 125A LSI
MCCB h250 3P 70kA 125A LSI
HYC032H Rear connexion H250 4P
Rear connexion H250 4P
HEC126H MCCB h250 4P 70kA 125A LSI
MCCB h250 4P 70kA 125A LSI
HYC031H Rear connexion H250 3P
Rear connexion H250 3P
HEC250H MCCB h250 3P 70kA 250A LSI
MCCB h250 3P 70kA 250A LSI
HEC251H MCCB h250 4P 70kA 250A LSI
MCCB h250 4P 70kA 250A LSI
HYC028H Terminal cover for collar term. h250 4P
Terminal cover for collar term. h250 4P
*All data is subject to errors and technical modifications. All prices are recommended retail prices.