AD120B

AD120B RCBO 1M 1P 10kA C-20A 30mA  A

AD120B

RCBO 1M 1P 10kA C-20A 30mA A

Cat. Ref.:AD120B
pc.
EAN No.:

3250611068594

Pack Qty.:1 pc.
ex. GST*:180.98 $ / pc.
inc. GST*:199.08 $ / pc.
Price Group:18000
Technical Characteristics
Neutral position:right
Number of protected poles:1
Number of poles:1 P
Type of pole:1 P
Curve:C
With fault indicator:no
Frequency:50 Hz
Rated short circuit breaking capacity Icn AC according IEC60898-1:10 kA
Rated operational voltage Ue:230/240 V
Rated insulation voltage:250 V
Max operating voltage:253 V
Rated impulse withstand voltage:4000 V
Rated residual operating current:30 mA
Withstand not tripping on 8-20 μs wave:3 kA
Rated short circuit breaking capacity Icn under 230V AC according IEC60898-1:10 kA
Breaking and opening capacity:6 kA
Magnetic regulating currrent at 40° C:5/10 In
min/maxi threshold value of the AC thermal operation:1,13/1,45 In
Rating current -15°C:24,73 A
Rating current -20°C:25,25 A
Rating current 0°C:23,15 A
Rating current 10°C:22,1 A
Rating current -10°C:24,2 A
Rating current 15°C:21,58 A
Rating current 20°C:21,05 A
Rating current 25°C:20,53 A
Rating current -25°C:25,78 A
Rating current 30°C:20 A
Rating current 35°C:19,6 A
Rating current 40°C:19,2 A
Rating current 45°C:18,8 A
Rating current 5°C:22,63 A
Rating current -5°C:23,68 A
Rating current 50°C:18,4 A
Rating current 55°C:18 A
Rating current 60°C:17,6 A
Correction factor of rating current for 2 devices placed side-by-side:1
Correction factor of rating current for 3 devices placed side-by-side:0,95
Correction factor of rating current for 4 and 5 devices placed side-by-side:0,9
Correction factor of rating current for 6 devices placed side-by-side:0,85
Power loss per pole at In:2,98 W
Total power loss under IN:5,76 W
Protected against nuisance tripping:no
Electric endurance in number of cycles:2000
Number of mechanical operations:1000
Depth of installed product:70 mm
Height of installed product:115 mm
Width of installed product:17,5 mm
Tightening torque:2,1Nm
Connection cross-section at output with screw, for flexible conductor:1/16 mm²
Connection cross-section of the access with screws, with flexible conductor:1/16 mm²
Connection cross-section at output with screw, for massive conductor:1/25 mm²
Connection cross-section for rigid conductor, upstream terminals with screws:1/25 mm²
Can be accessorized:no
Standard text:IEC 61009-1, AS/NZS 61009-1
European directive WEEE:not concerned
Protection index IP:IP20
Residual current type:A
Degree of pollution according to IEC 60664 / IEC 60947-2:2
Class of energy limitation I²t:3
Altitude:2000 m
Air humidity protection:Execution II
  • AD120B
    AD120B RCBO 1M 1P 10kA C-20A 30mA  A
    AD120B
  • AD120B RCBO 1M 1P 10kA C-20A 30mA  A
Visitors who viewed this product also viewed the following products
ADA120T RCBO 1P 6kA C-20A 30mA A
RCBO 1P 6kA C-20A 30mA A
AD116B RCBO 1M 1P 10kA C-16A 30mA  A
RCBO 1M 1P 10kA C-16A 30mA A
AD110B RCBO 1M 1P 10kA C-10A 30mA  A
RCBO 1M 1P 10kA C-10A 30mA A
AD125B RCBO 1M 1P 10kA C-25A 30mA  A
RCBO 1M 1P 10kA C-25A 30mA A
AD132B RCBO 1M 1P 10kA C-32A 30mA  A
RCBO 1M 1P 10kA C-32A 30mA A
ACA566T RCBO 1P+N 10kA C-16A 10mA A
RCBO 1P+N 10kA C-16A 10mA A
ADA110T RCBO 1P 6kA C-10A 30mA A
RCBO 1P 6kA C-10A 30mA A
ADC320T RCBO 1P 6kA C-20A 30mA A Class 1M
RCBO 1P 6kA C-20A 30mA A Class 1M
AD106B RCBO 1M 1P 10kA C-6A 30mA  A
RCBO 1M 1P 10kA C-6A 30mA A
ADA106T RCBO 1P 6kA C-6A 30mA A
RCBO 1P 6kA C-6A 30mA A
RCBO 1M 1P 10kA C-20A 10mA A
ACA563T RCBO 1P+N 10kA C-13A 10mA A
RCBO 1P+N 10kA C-13A 10mA A
ADA116T RCBO 1P 6kA C-16A 30mA A
RCBO 1P 6kA C-16A 30mA A
ADA306T RCBO ELE 1P+N 4,5kA C-6A 30mA A
RCBO ELE 1P+N 4, 5kA C-6A 30mA A
*All data is subject to errors and technical modifications. All prices are recommended retail prices.