  • e-Catalogue
  • Downloads,
    Services & Support
  • News, Exhibitions
    & Case Studies
  • AS/NZS 3000:2018
    Wiring Rules
  • About Us

HHA018Z

HHA018Z MCCB h3 x160 TM 1x20A 25kA

HHA018Z

MCCB h3 x160 TM 1x20A 25kA

Cat. Ref.:HHA018Z
pc.
EAN No.:

3250613135959

Pack Qty.:1 pc.
ex. GST*:199.77 $ / pc.
inc. GST*:219.75 $ / pc.
Price Group:15150
Technical Characteristics
Neutral position:without neutral
Number of protected poles:1
Number of poles:1 P
Type of pole:1P1D
Trip Unit:TM F/F
Concurrently switching N-neutral:no
Compatible with DIN rail mounting:no
Motor drive integrated:no
Rated operational voltage Ue:220 / 240 V
Frequency:50/60 Hz
Rated insulation voltage:690 V
Rated impulse withstand voltage:8 kV
With under voltage release:no
Rated current:20 A
Thermal protection nob setting xIN:1
Rating current 10°C according to IEC 60947:25,4 A
Rating current 150°C according to IEC 60947:24,8 A
Rating current 20°C according to IEC 60947:24,2 A
Rating current 25°C according to IEC 60947:23,5 A
Rating current 30°C according to IEC 60947:22,8 A
Rating current 35°C according to IEC 60947:22,2 A
Rating current 40°C according to IEC 60947:21,4 A
Rating current 45°C according to IEC 60947:20,7 A
Rating current 50°C according to IEC 60947:20 A
Rating current 55°C according to IEC 60947:19,2 A
Rating current 60°C according to IEC 60947:18,3 A
Rating current 65°C according to IEC 60947:17,5 A
Rating current 70°C according to IEC 60947:16,6 A
Rated service breaking capacity Ics under 220V AC according IEC 60947-2:25 kA
Rated service breaking capacity Ics under 230V AC according IEC 60947-2:25 kA
Rated service breaking capacity Ics under 240V AC according IEC 60947-2:25 kA
Rated service breaking capacity Ics under 380V AC according IEC 60947-2:20 kA
Rated service breaking capacity Ics under 400V AC according IEC 60947-2:20 kA
Rated service breaking capacity Ics under 415V AC according IEC 60947-2:20 kA
Rated ultimate short-circuit breaking capacity Icu under 230V AC IEC 60947-2:35 kA
Rated ultimate short-circuit breaking capacity Icu under 240V AC IEC 60947-2:35 kA
Rated ultimate short-circuit breaking capacity Icu under 400V AC IEC 60947-2:25 kA
Rated ultimate short-circuit breaking capacity Icu under 415V AC IEC 60947-2:25 kA
Range of the thermal adjustment:20 A
Rated ultimate short-circuit breaking capacity Icu under 380V AC IEC 60947-2:25 kA
Frequency:50 to 60 Hz
Total power loss under IN:2,7 W
Power loss per pole at In:2,7 W
Electric endurance in number of cycles:1000
Number of mechanical operations:4000
Depth of installed product:68 mm
Height of installed product:130 mm
Width of installed product:25 mm
Critical distance switching emission/earthed part bottom:40 mm
Critical distance switching emission/earthed part left:50 mm
Critical distance switching emission/earthed part right:50 mm
Critical distance switching emission/earthed part top:40 mm
Critical distance switching emission/insulated plate:30 mm
Critical distance switching emission/live part:50 mm
Type of connection:with screw
Range of the magnetic adjustment:600 A
Can be accessorized:yes
Standard text:IEC 60947-2
European directive WEEE:concerned
Product categories described in the W3E directive 2012/19/EU:Category 5
Protection index IP:IP4X
Degree of pollution according to IEC 60664 / IEC 60947-2:3
Altitude:2000 m
Temperature of calibration:50 °C
  • HHA018Z
    HHA018Z MCCB h3 x160 TM 1x20A 25kA
    HHA018Z
  • HHA018Z MCCB h3 x160 TM 1x20A 25kA
*All data is subject to errors and technical modifications. All prices are recommended retail prices.