  • e-Catalogue
  • Downloads,
    Services & Support
  • News, Exhibitions
    & Case Studies
  • AS/NZS 3000:2018
    Wiring Rules
  • About Us

HHA061Z

HHA061Z MCCB h3 x160 TM 1x63A 25kA

HHA061Z

MCCB h3 x160 TM 1x63A 25kA

Cat. Ref.:HHA061Z
pc.
EAN No.:

3250613136000

Pack Qty.:1 pc.
ex. GST*:194.90 $ / pc.
inc. GST*:214.39 $ / pc.
Price Group:15150
Technical Characteristics
Neutral position:without neutral
Number of protected poles:1
Number of poles:1 P
Type of pole:1P1D
Trip Unit:TM F/F
Concurrently switching N-neutral:no
Compatible with DIN rail mounting:no
Motor drive integrated:no
Rated operational voltage Ue:220 / 240 V
Frequency:50/60 Hz
Rated insulation voltage:690 V
Rated impulse withstand voltage:8 kV
With under voltage release:no
Rated current:63 A
Thermal protection nob setting xIN:1
Rating current 10°C according to IEC 60947:76,8 A
Rating current 150°C according to IEC 60947:75,2 A
Rating current 20°C according to IEC 60947:73,6 A
Rating current 25°C according to IEC 60947:71,9 A
Rating current 30°C according to IEC 60947:70,2 A
Rating current 35°C according to IEC 60947:68,5 A
Rating current 40°C according to IEC 60947:66,7 A
Rating current 45°C according to IEC 60947:64,8 A
Rating current 50°C according to IEC 60947:63 A
Rating current 55°C according to IEC 60947:61 A
Rating current 60°C according to IEC 60947:59 A
Rating current 65°C according to IEC 60947:56,9 A
Rating current 70°C according to IEC 60947:54,7 A
Rated service breaking capacity Ics under 220V AC according IEC 60947-2:25 kA
Rated service breaking capacity Ics under 230V AC according IEC 60947-2:25 kA
Rated service breaking capacity Ics under 240V AC according IEC 60947-2:25 kA
Rated service breaking capacity Ics under 380V AC according IEC 60947-2:20 kA
Rated service breaking capacity Ics under 400V AC according IEC 60947-2:20 kA
Rated service breaking capacity Ics under 415V AC according IEC 60947-2:20 kA
Rated ultimate short-circuit breaking capacity Icu under 230V AC IEC 60947-2:35 kA
Rated ultimate short-circuit breaking capacity Icu under 240V AC IEC 60947-2:35 kA
Rated ultimate short-circuit breaking capacity Icu under 400V AC IEC 60947-2:25 kA
Rated ultimate short-circuit breaking capacity Icu under 415V AC IEC 60947-2:25 kA
Range of the thermal adjustment:63 A
Rated ultimate short-circuit breaking capacity Icu under 380V AC IEC 60947-2:25 kA
Frequency:50 to 60 Hz
Total power loss under IN:5,1 W
Power loss per pole at In:5,1 W
Electric endurance in number of cycles:1000
Number of mechanical operations:4000
Depth of installed product:68 mm
Height of installed product:130 mm
Width of installed product:25 mm
Critical distance switching emission/earthed part bottom:40 mm
Critical distance switching emission/earthed part left:50 mm
Critical distance switching emission/earthed part right:50 mm
Critical distance switching emission/earthed part top:40 mm
Critical distance switching emission/insulated plate:30 mm
Critical distance switching emission/live part:50 mm
Type of connection:with screw
Range of the magnetic adjustment:1000 A
Can be accessorized:yes
Standard text:IEC 60947-2
European directive WEEE:concerned
Product categories described in the W3E directive 2012/19/EU:Category 5
Protection index IP:IP4X
Degree of pollution according to IEC 60664 / IEC 60947-2:3
Altitude:2000 m
Temperature of calibration:50 °C
  • HHA061Z
    HHA061Z MCCB h3 x160 TM 1x63A 25kA
    HHA061Z
  • HHA061Z MCCB h3 x160 TM 1x63A 25kA
*All data is subject to errors and technical modifications. All prices are recommended retail prices.