HHA081U
MCCB h3 x160 TM 4x80A 25kA
Cat. Ref.: | HHA081U |
EAN No.: | 3250613131104 |
Pack Qty.: | 1 pc. |
ex. GST*: | 699.83 $ / pc. |
inc. GST*: | 769.81 $ / pc. |
Price Group: | 15150 |
Number of protected poles: | 4 |
Number of poles: | 4 P |
Type of pole: | 4P4D |
Trip Unit: | TM A/F |
Compatible with DIN rail mounting: | no |
Motor drive integrated: | no |
Rated operational voltage Ue: | 220 / 415 V |
Frequency: | 50/60 Hz |
Rated insulation voltage: | 690 V |
Rated impulse withstand voltage: | 8 kV |
With under voltage release: | no |
Rated current: | 80 A |
Thermal protection nob setting xIN: | 0,63 / 0,8 / 1 |
Rating current 10°C according to IEC 60947: | 93,2 A |
Rating current 150°C according to IEC 60947: | 91,6 A |
Rating current 20°C according to IEC 60947: | 90,1 A |
Rating current 25°C according to IEC 60947: | 88,5 A |
Rating current 30°C according to IEC 60947: | 86,8 A |
Rating current 35°C according to IEC 60947: | 85,2 A |
Rating current 40°C according to IEC 60947: | 83,5 A |
Rating current 45°C according to IEC 60947: | 81,7 A |
Rating current 50°C according to IEC 60947: | 80 A |
Rating current 55°C according to IEC 60947: | 78,1 A |
Rating current 60°C according to IEC 60947: | 76,3 A |
Rating current 65°C according to IEC 60947: | 74,4 A |
Rating current 70°C according to IEC 60947: | 72,4 A |
Rated service breaking capacity Ics under 220V AC according IEC 60947-2: | 25 kA |
Rated service breaking capacity Ics under 230V AC according IEC 60947-2: | 25 kA |
Rated service breaking capacity Ics under 240V AC according IEC 60947-2: | 25 kA |
Rated service breaking capacity Ics under 380V AC according IEC 60947-2: | 20 kA |
Rated service breaking capacity Ics under 400V AC according IEC 60947-2: | 20 kA |
Rated service breaking capacity Ics under 415V AC according IEC 60947-2: | 20 kA |
Rated ultimate short-circuit breaking capacity Icu under 230V AC IEC 60947-2: | 35 kA |
Rated ultimate short-circuit breaking capacity Icu under 240V AC IEC 60947-2: | 35 kA |
Rated ultimate short-circuit breaking capacity Icu under 400V AC IEC 60947-2: | 25 kA |
Rated ultimate short-circuit breaking capacity Icu under 415V AC IEC 60947-2: | 25 kA |
Range of the thermal adjustment: | 50 / 63 / 80 A |
Rated ultimate short-circuit breaking capacity Icu under 380V AC IEC 60947-2: | 25 kA |
Frequency: | 50 to 60 Hz |
Power loss per pole at 0.63*In: | 4,2 W |
Power loss per pole at 0.8*In: | 6,6 W |
Total power loss at 0.63*In: | 12,5 W |
Total power loss at 0.8*In: | 19,9 W |
Total power loss under IN: | 32,1 W |
Power loss per pole at In: | 10,7 W |
Electric endurance in number of cycles: | 1000 |
Number of mechanical operations: | 4000 |
Depth of installed product: | 68 mm |
Height of installed product: | 130 mm |
Width of installed product: | 100 mm |
Critical distance switching emission/earthed part bottom: | 40 mm |
Critical distance switching emission/earthed part left: | 50 mm |
Critical distance switching emission/earthed part right: | 50 mm |
Critical distance switching emission/earthed part top: | 40 mm |
Critical distance switching emission/insulated plate: | 30 mm |
Critical distance switching emission/live part: | 50 mm |
Type of connection: | with screw |
Range of the magnetic adjustment: | 1000 A |
Can be accessorized: | yes |
Standard text: | IEC 60947-2 |
European directive WEEE: | concerned |
Product categories described in the W3E directive 2012/19/EU: | Category 5 |
Protection index IP: | IP4X |
Degree of pollution according to IEC 60664 / IEC 60947-2: | 3 |
Altitude: | 2000 m |
Temperature of calibration: | 50 °C |