HHA100U

HHA100U MCCB h3 x160 TM 3x100A 25kA

HHA100U

MCCB h3 x160 TM 3x100A 25kA

Cat. Ref.:HHA100U
pc.
EAN No.:

3250613130770

Pack Qty.:1 pc.
ex. GST*:813.64 $ / pc.
inc. GST*:895.00 $ / pc.
Price Group:15150
Technical Characteristics
Neutral position:without neutral
Number of protected poles:3
Number of poles:3 P
Type of pole:3P3D
Trip Unit:TM A/F
Concurrently switching N-neutral:no
Compatible with DIN rail mounting:no
Motor drive integrated:no
Rated operational voltage Ue:220 / 415 V
Frequency:50/60 Hz
Rated insulation voltage:690 V
Rated impulse withstand voltage:8 kV
With under voltage release:no
Rated current:100 A
Thermal protection nob setting xIN:0,63 / 0,8 / 1
Rating current 10°C according to IEC 60947:121,6 A
Rating current 150°C according to IEC 60947:119,1 A
Rating current 20°C according to IEC 60947:116,6 A
Rating current 25°C according to IEC 60947:114 A
Rating current 30°C according to IEC 60947:111,3 A
Rating current 35°C according to IEC 60947:108,6 A
Rating current 40°C according to IEC 60947:105,8 A
Rating current 45°C according to IEC 60947:102,9 A
Rating current 50°C according to IEC 60947:100 A
Rating current 55°C according to IEC 60947:96,9 A
Rating current 60°C according to IEC 60947:93,8 A
Rating current 65°C according to IEC 60947:90,5 A
Rating current 70°C according to IEC 60947:87,1 A
Rated service breaking capacity Ics under 220V AC according IEC 60947-2:25 kA
Rated service breaking capacity Ics under 230V AC according IEC 60947-2:25 kA
Rated service breaking capacity Ics under 240V AC according IEC 60947-2:25 kA
Rated service breaking capacity Ics under 380V AC according IEC 60947-2:20 kA
Rated service breaking capacity Ics under 400V AC according IEC 60947-2:20 kA
Rated service breaking capacity Ics under 415V AC according IEC 60947-2:20 kA
Rated ultimate short-circuit breaking capacity Icu under 230V AC IEC 60947-2:35 kA
Rated ultimate short-circuit breaking capacity Icu under 240V AC IEC 60947-2:35 kA
Rated ultimate short-circuit breaking capacity Icu under 400V AC IEC 60947-2:25 kA
Rated ultimate short-circuit breaking capacity Icu under 415V AC IEC 60947-2:25 kA
Range of the thermal adjustment:63 / 80 / 100 A
Rated ultimate short-circuit breaking capacity Icu under 380V AC IEC 60947-2:25 kA
Frequency:50 to 60 Hz
Power loss per pole at 0.63*In:4,7 W
Power loss per pole at 0.8*In:7,6 W
Total power loss at 0.63*In:14,2 W
Total power loss at 0.8*In:22,9 W
Total power loss under IN:35,7 W
Power loss per pole at In:11,9 W
Electric endurance in number of cycles:1000
Number of mechanical operations:4000
Depth of installed product:68 mm
Height of installed product:130 mm
Width of installed product:75 mm
Critical distance switching emission/earthed part bottom:40 mm
Critical distance switching emission/earthed part left:50 mm
Critical distance switching emission/earthed part right:50 mm
Critical distance switching emission/earthed part top:40 mm
Critical distance switching emission/insulated plate:30 mm
Critical distance switching emission/live part:50 mm
Type of connection:with screw
Range of the magnetic adjustment:1500 A
Can be accessorized:yes
Standard text:IEC 60947-2
European directive WEEE:concerned
Product categories described in the W3E directive 2012/19/EU:Category 5
Protection index IP:IP4X
Degree of pollution according to IEC 60664 / IEC 60947-2:3
Altitude:2000 m
Temperature of calibration:50 °C
  • HHA100U
    HHA100U MCCB h3 x160 TM 3x100A 25kA
    HHA100U
  • HHA100U MCCB h3 x160 TM 3x100A 25kA
Visitors who viewed this product also viewed the following products
ESC080 Auxiliary contact 6A,  1NO+1NC
Auxiliary contact 6A, 1NO+1NC
HHA101U MCCB h3 x160 TM 4x100A 25kA
MCCB h3 x160 TM 4x100A 25kA
HR510 EARTH LEAKAGE RELAY 0.03-10A TIME DELAY
EARTH LEAKAGE RELAY 0.03-10A TIME DELAY
HHA030Z MCCB X160 1P 25kA 32A
MCCB X160 1P 25kA 32A
HNF980H MCCB h1600 3P 50kA 1250A LSI
MCCB h1600 3P 50kA 1250A LSI
HXD040H Motor operator h400-h630 24-48V DC
Motor operator h400-h630 24-48V DC
HYC027H Terminal cover for collar term. h250 3P
Terminal cover for collar term. h250 3P
MSN140 MCB 1P 6kA C-40A 1M
MCB 1P 6kA C-40A 1M
ADA940T RCBO 1P+N 6kA C-40A 30mA A Class
RCBO 1P+N 6kA C-40A 30mA A Class
HA457 Load break switch 4P 400A
Load break switch 4P 400A
HEE970H MCCB h1000 3P 70kA 1000A LSI
MCCB h1000 3P 70kA 1000A LSI
HMD390T MCB 3P 15kA D-100A 4.5M
MCB 3P 15kA D-100A 4.5M
HMF399T MCB 3P 10kA C-125A 4.5M
MCB 3P 10kA C-125A 4.5M
HNC040H MCCB h250 3P 50kA 40A LSI
MCCB h250 3P 50kA 40A LSI
HXA030H Direct rotary handle x160
Direct rotary handle x160
*All data is subject to errors and technical modifications. All prices are recommended retail prices.