NDN250A

NDN250A MCB 2P 10kA/15kA D-50A 2M

NDN250A
NDN250A MCB 2P 10kA/15kA D-50A 2M
NDN250A MCB 2P 10kA/15kA D-50A 2M

MCB 2P 10kA/15kA D-50A 2M

Cat. Ref.:NDN250A
pc.
EAN No.:

3250614619144

Pack Qty.:6 pc.
ex. GST*:202.05 $ / pc.
inc. GST*:222.26 $ / pc.
Price Group:14220
Technical Characteristics
Neutral position:without neutral
Number of protected poles:2
Number of poles:2 P
Type of pole:2 P
Fixing mode:Din-Rail
Curve:D
Concurrently switching N-neutral:no
Compatible with DIN rail mounting:yes
With fault indicator:no
Top connection alignement for modular devices:Aligned terminal
Bottom connection alignement for modular devices:Aligned terminal
Rated short circuit breaking capacity Icn AC according IEC60898-1:10 kA
Rated operational voltage Ue:400 V
Type of supply voltage:AC
Rated insulation voltage:500 V
Rated impulse withstand voltage:6000 V
Minimum threshold voltage (Ue min):12 V
Rated current:50 A
Rated service breaking capacity Ics AC according IEC 60898-1:7,5 kA
min/maxi threshold value of the AC thermal operation:1,13 / 1,45 In
Magnetic regulating currrent:10 / 14,4 In
min/maxi threshold value of the DC magnetic operation:15 / 30 In
min/maxi threshold value of the DC thermal operation:1,13 / 1,45 In
Rating current -10°C according to IEC 60947:71,01 A
Rating current -15°C according to IEC 60947:72,49 A
Rating current -20°C according to IEC 60947:73,93 A
Rating current -25°C according to IEC 60947:75,35 A
Rating current -5°C according to IEC 60947:69,5 A
Rating current 0°C according to IEC 60947:67,96 A
Rating current 10°C according to IEC 60947:64,77 A
Rating current 150°C according to IEC 60947:63,11 A
Rating current 20°C according to IEC 60947:61,41 A
Rating current 25°C according to IEC 60947:59,66 A
Rating current 30°C according to IEC 60947:57,86 A
Rating current 35°C according to IEC 60947:56 A
Rating current 40°C according to IEC 60947:54,07 A
Rating current 45°C according to IEC 60947:52,08 A
Rating current 5°C according to IEC 60947:66,38 A
Rating current 50°C according to IEC 60947:50 A
Rating current 55°C according to IEC 60947:47,83 A
Rating current 60°C according to IEC 60947:45,57 A
Rating current 65°C according to IEC 60947:43,18 A
Rating current 70°C according to IEC 60947:40,65 A
Rated service breaking capacity Ics under 220V AC according IEC 60947-2:15 kA
Rated service breaking capacity Ics under 230V AC according IEC 60947-2:15 kA
Rated service breaking capacity Ics under 240V AC according IEC 60947-2:15 kA
Rated service breaking capacity Ics under 380V AC according IEC 60947-2:7,5 kA
Rated service breaking capacity Ics under 400V AC according IEC 60947-2:7,5 kA
Rated service breaking capacity Ics under 415V AC according IEC 60947-2:7,5 kA
Rated short circuit breaking capacity Icn under 230V AC according IEC60898-1:10 kA
Rated short circuit breaking capacity Icn under 400V AC according IEC60898-1:10 kA
Rated ultimate short-circuit breaking capacity Icu under 230V AC IEC 60947-2:30 kA
Rated ultimate short-circuit breaking capacity Icu under 240V AC IEC 60947-2:30 kA
Rated ultimate short-circuit breaking capacity Icu under 400V AC IEC 60947-2:15 kA
Rated ultimate short-circuit breaking capacity Icu under 415V AC IEC 60947-2:15 kA
Rated short circuit breaking capacity Icn under 240V AC according IEC 60898-1:10 kA
Rated short circuit breaking capacity Icn under 380V AC according IEC 60898-1:10 kA
Rated short circuit breaking capacity Icn under 415V AC according IEC 60898-1:10 kA
Rated service breaking capacity Ics under 220V AC according IEC 60898-1:7,5 kA
Rated service breaking capacity Ics under 230V AC according IEC 60898-1:7,5 kA
Rated service breaking capacity Ics under 240V AC according IEC 60898-1:7,5 kA
Rated service breaking capacity Ics under 380V AC according IEC 60898-1:7,5 kA
Rated service breaking capacity Ics under 400V AC according IEC 60898-1:7,5 kA
Rated service breaking capacity Ics under 415V AC according IEC 60898-1:7,5 kA
Rated ultimate short-circuit breaking capacity Icu under 220V AC IEC 60947-2:30 kA
Rated ultimate short-circuit breaking capacity Icu under 380V AC IEC 60947-2:15 kA
Rating current -25°C:65,12 A
Rating current -20°C:63,89 A
Rating current -15°C:62,64 A
Rating current -10°C:61,37 A
Rating current -5°C:60,15 A
Rating current 0°C:58,92 A
Rating current 5°C:57,69 A
Rating current 10°C:56,47 A
Rating current 25°C:52,84 A
Rating current 30°C:50 A
Rating current 35°C:49,4 A
Rating current 40°C:48,22 A
Rating current 45°C:46,72 A
Rating current 50°C:46,96 A
Rating current 55°C:42,77 A
Rating current 60°C:40,33 A
Rating current 65°C:37,57 A
Rating current 70°C:34,49 A
Correction factor of rating current for 2 devices placed side-by-side:1
Correction factor of rating current for 3 devices placed side-by-side:0,95
Correction factor of rating current for 4 and 5 devices placed side-by-side:0,9
Correction factor of rating current for 6 devices placed side-by-side:0,85
Correction factor of magnetic tripping with 100 Hz:1,1
Correction factor of magnetic tripping with 200 Hz:1,2
Correction factor of magnetic tripping with 400 Hz:1,5
Correction factor of magnetic tripping with 60 Hz:1,1
Frequency:50 to 60 Hz
Maximum power loss per pole according to the product standard:9 W
Total power loss under IN:10,6 W
Power loss per pole at In:5,65 W
Electric endurance in number of cycles:4000
Number of mechanical operations:20000
Depth of installed product:70 mm
Height of installed product:83 mm
Width of installed product:35 mm
Type of top connection for modular devices:with screw
Tightening torque:2,8Nm
Type of top rail clip for modular devices:NA
Type of bottom rail clip for modular devices:plastic
Type of Bottom Connection for modular devices:BIconnect
Top removability for modular devices:yes
Bottom removability for modular devices:yes
Suitable for flush-mounting:yes
360° product mounting position:yes
Connection cross-section at output with screw, for flexible conductor:1 / 25 mm²
Connection cross-section at output with screw, for massive conductor:1 / 35 mm²
Connection cross-section for rigid conductor, upstream terminals with screws:1 / 35 mm²
Connection cross-section of the access with screws, with flexible conductor:1 / 25 mm²
Downstream cage clamp delivery status:opened
Upstream cage clamp delivery status:opened
Can be accessorized:yes
With transparent product label holder:yes
Standard text:EN 60898-1, IEC 60947-2
European directive WEEE:concerned
Product categories described in the W3E directive 2012/19/EU:Category 5
Protection index IP:IP20
Operating temperature:-25…70 °C
Degree of pollution according to IEC 60664 / IEC 60947-2:2
Altitude:2000 m
Storage/transport temperature:-25…80 °C
Temperature of calibration:50 °C
  • NDN250A
    NDN250A MCB 2P 10kA/15kA D-50A 2M
    NDN250A
  • NDN250A
    NDN250A MCB 2P 10kA/15kA D-50A 2M
    NDN250A
  • NDN250A MCB 2P 10kA/15kA D-50A 2M
  • NDN250A MCB 2P 10kA/15kA D-50A 2M
Visitors who viewed this product also viewed the following products
HA356 Load break switch 3P 400A
Load break switch 3P 400A
HNC125H MCCB h250 3P 50kA 125A LSI
MCCB h250 3P 50kA 125A LSI
HA354 Load break switch 3P 250A
Load break switch 3P 250A
HMD499T MCB 4P 15kA D-125A 6M
MCB 4P 15kA D-125A 6M
HXC001H Shunt trip Release 24V DC(h250...1000)
Shunt trip Release 24V DC(h250...1000)
ESC441 Contactor 40A,  4NC,  230V
Contactor 40A, 4NC, 230V
HA457 Load break switch 4P 400A
Load break switch 4P 400A
HND630H MCCB h630 3P 50kA 630A LSI
MCCB h630 3P 50kA 630A LSI
HXF039H Padlock H1250-H1600
Padlock H1250-H1600
HYB001H Collar terminal x250 Al/Cu 3P
Collar terminal x250 Al/Cu 3P
MZ203 Shunt trip 230-415V AC 110-130V DC
Shunt trip 230-415V AC 110-130V DC
HA362 Load break switch 3P 1250A
Load break switch 3P 1250A
HNC040H MCCB h250 3P 50kA 40A LSI
MCCB h250 3P 50kA 40A LSI
HXC042H Motor operator h250 230-240VAC
Motor operator h250 230-240VAC
HXF042H Motor operator H1250-H1600 200-230VAC
Motor operator H1250-H1600 200-230VAC
*All data is subject to errors and technical modifications. All prices are recommended retail prices.